Liquid Refrigerant Receivers Vertical
Liquid Refrigerant Receivers Vertical
Liquid Refrigerant Receivers Vertical

Liquid Refrigerant Receivers Vertical

Liquid Refrigerant Receivers are designed to hold excess liquid that would otherwise back up in the Condenser Coil and essentially reduce the size of the Condenser Coil.
During pump down, Receivers also act as a holding tank.

  • Description
  • Key Featuers
  • Drawing & Models Table
  • Data Sheet

Liquid Refrigerant Receivers are designed to hold excess liquid that would otherwise back up in the Condenser Coil and essentially reduce the size of the Condenser Coil.

During pump down, Receivers also act as a holding tank.


Recommended For: Liquid Line Receivers are designed for installation in the liquid line of any HVAC&R Units.


These Receivers are designed for installation in the liquid line of any refrigeration or air conditioning application which requires a storage vessel for liquid refrigerant either for system pump downs or as a safeguard to ensure that a solid column of liquid is in the liquid line.


  • Capacity Range: From 1 Litre to 60 Litres.

  • Available in Vertical & Horizontal Type.

  • Connection Type: Solder or/and Rotolock Thread

  • Accessories: Provision for a Pressure Relief valve, Fusible Plug, Sight Glass, Rotolock Valve.

  • Certificate: UL & CE (Available on request).

  • Ability to Design & Manufacture Custom Built Capacities of Receivers

DIMENSIONAL DATA


DIMENSIONAL DATA
No. Model No. Internal Volume Capacity (Liters)* Pump Down Capacity (KG) Connection Dimension Mounting Option Refer Drawing No. Liquid Indicator Inbuilt Fusible Plug
Inlet Outlet ØA mm inch B mm inch C mm inch D mm inch E mm inch
NON-UL LISTED
1 LRRV-3350-3SX3S-H 1.4 1.4 3/8" ODF
(COPPER)
3/8" ODF
(COPPER)
76.2 3 350 13.78 41 1.62 NA NA NA NA M8 X1.25
Bolt & Nut
1 Not Applicable Not Applicable
2 LRRV-3482-3SX3S-H 2.0 1.9 482 18.87 41 1.62 NA NA NA NA
3 LRRV-5296-3SX5R-H 2.9 2.3 1/2" ODF
(COPPER)
1/2" ODF
(COPPER)
127 5 296 11.65 183 7.20 60 2.36 NA NA M10 X 1.5
Bolt & Nut
2 Yes
4 LRRV-5376-4SX5R-H 4.2 3.4 376 14.81 74 2.91
5 LRRV-5456-4SX5R-H 4.65 3.75 456 17.96 86 3.38
6 LRRV-5536-4SX5R-H 6.1 5.0 536 21.11 106 4.17
6 LRRV-5536-4SX5R-H 6.1 5.0 1/2" ODF (COPPER) 1"-14 UNS 127 5 536 21.11 180 7.08 109 4.17 150 5.90 Round Flange 3 Not Applicable
7 LRRV-5566-5SX5R-H 6.4 5.3 5/8" ODF (COPPER) 1"-14 UNS 152.4 6 566 22.28 183 7.20 111 4.37 150 5.90 Round Flange 3 Not Applicable
8 LRRV-6465-4SX5R-H 7.4 6.1 1/2" ODF (COPPER) 1"-14 UNS 152.4 6 465 18.31 157 6.18 93 3.66 150 5.90 Round Flange 3 Not Applicable
9 LRRV-6526-5SX5R-H 8.4 6.9 5/8" ODF (COPPER) 1"-14 UNS 152.4 6 526 20.71 155 6.10 109 4.17 172 6.77 Round Flange 3 Not Applicable
10 LRRV-6587-5SX5R-H 9.5 7.7 5/8" ODF (COPPER) 1"-14 UNS 152.4 6 587 23.12 160 6.29 117 4.60 172 6.77 Round Flange 3 Not Applicable
11 LRRV-6648-5SX5R-H 10.4 8.6 5/8" ODF (COPPER) 1"-14 UNS 152.4 6 648 25.52 160 6.29 128 5.03 172 6.77 Round Flange 3 Not Applicable
12 LRRV-6709-5SX5R-H 11.4 9.4 5/8" ODF (COPPER) 1"-14 UNS 152.4 6 709 27.92 160 6.29 139 5.47 172 6.77 Round Flange 3 Not Applicable
13 LRRV-6770-7SX7R-H 12.1 10 7/8" ODF (COPPER) 1-1/4"-12 UNF 152.4 6 770 30.32 179 7.04 145 5.70 172 6.77 Round Flange 3 Not Applicable
DIMENSIONAL DATA
No. Model No. Internal Volume Capacity (Liters)* Pump Down Capacity (KG) Connection Dimension Mounting Option Refer Drawing No. Liquid Indicator Inbuilt Fusible Plug
Inlet Outlet ØA mm inch B mm inch C mm inch D mm inch E mm inch
NON-UL LISTED
1 LRRV-3350-3SX3S 1.4 1.4 3/8" ODF
(COPPER)
3/8" ODF
(COPPER)
76.2 3 350 13.78 41 1.62 NA NA NA NA M8 X1.25
Bolt & Nut
1 Not Applicable Not Applicable
2 LRRV-3482-3SX3S 2.0 1.9 482 18.87 41 1.62 NA NA NA NA
3 LRRV-5296-3SX5R 2.9 2.3 1/2" ODF
(COPPER)
1/2" ODF
(COPPER)
127 5 296 11.65 183 7.20 60 2.36 NA NA M10 X 1.5
Bolt & Nut
2 Yes
4 LRRV-5376-4SX5R 4.2 3.4 376 14.81 74 2.91
5 LRRV-5456-4SX5R 4.65 3.75 456 17.96 86 3.38
6 LRRV-5536-4SX5R 6.1 5.0 536 21.11 106 4.17
7 LRRV-5566-5SX5R 6.4 5.3 5/8" ODF (COPPER) 1"-14 UNS 152.4 6 566 22.28 183 7.20 111 4.37 150 5.90 Round Flange 3 Not Applicable
8 LRRV-6465-4SX5R 7.4 6.1 1/2" ODF (COPPER) 1"-14 UNS 152.4 6 465 18.31 157 6.18 93 3.66 150 5.90 Round Flange 3 Not Applicable
9 LRRV-6526-5SX5R 8.4 6.9 5/8" ODF (COPPER) 1"-14 UNS 152.4 6 526 20.71 155 6.10 109 4.17 172 6.77 Round Flange 3 Not Applicable
10 LRRV-6587-5SX5R 9.5 7.7 5/8" ODF (COPPER) 1"-14 UNS 152.4 6 587 23.12 160 6.29 117 4.60 172 6.77 Round Flange 3 Not Applicable
11 LRRV-6648-5SX5R 10.4 8.6 5/8" ODF (COPPER) 1"-14 UNS 152.4 6 648 25.52 160 6.29 128 5.03 172 6.77 Round Flange 3 Not Applicable
12 LRRV-6709-5SX5R 11.4 9.4 5/8" ODF (COPPER) 1"-14 UNS 152.4 6 709 27.92 160 6.29 139 5.47 172 6.77 Round Flange 3 Not Applicable
13 LRRV-6770-7SX7R 12.1 10 7/8" ODF (COPPER) 1-1/4"-12 UNF 152.4 6 770 30.32 179 7.04 145 5.70 172 6.77 Round Flange 3 Not Applicable
14 LRRV-8446-7R(B) 15 10.3 1-1/4" 12 UNF 1-1/4" 12 UNF 219 8 446 17.56 492 19.37 332 13.07 276.7 10.89 Bracket 4
15 LRRV-8446-7SX5R(F) 15 10.3 7/8" ODF (COPPER) 1"-14 UNS* 219 8 446 17.56 224 8.82 357 14.06 175 6.88 Round Flange 5 Available No
16 LRRV-8530-7RX7R(F) 18 13.2 1-1/4"-12 UNF* 1-1/4"-12 UNF* 530 20.87 441 19.09 6
17 LRRV-8588-7RX7R(F) 19.9 15.1 1-1/4"-12 UNF* 1-1/4"-12 UNF* 588 23.15 499 19.65 6
18 LRRV-8732-7RX7R(F) 25 20.4 1-1/4"-12 UNF* 1-1/4"-12 UNF* 732 28.82 643 25.31 6

Liquid Receiver - Installation Guideline

FAQ: ‘Dry All’ Liquid Refrigeration Receivers

Why a Liquid Refrigerant Receiver (Receiver) is required in HVAC&R System?

Receiver is a storage vessel designed to hold excess refrigerant which is not in circulation. Refrigeration systems exposed to varying heat loads, or systems utilizing a condenser flooding valve to maintain a minimum head pressure during low ambient temperatures will need a receiver to store excess refrigerant.


Receiver also plays a key role in a HVAC&R system as it ensures that only liquid refrigerant should enter the expansion device.Due to density difference during cycle operation, liquid refrigerant is accumulated at the bottom of the receiver and remaining volume is occupied by the vapor refrigerant. Receiver also acts as a reservoir during system pump down.

How does a Receiver work and serve the purpose?

Liquid + Vapor refrigerant will enter the Receiver from ‘Inlet’ which is normally at the top / upper side of the receiver and is free flowing. The vapour will be always at the top and liquid at the bottom of the Receiver. The outlet connection of the Receiver is through a dip tube of which the pickup point is at the lowest level of Receiver. This dip tube will always pick up only liquid from the bottom of the Receiver.

Where is Receiver installed in HVAC&R system?

The receiver is installed in the liquid line (i.e. the part of the refrigeration cycle where the refrigerant is in the liquid phase) and is located after the condenser in a refrigeration system. It is installed between the condenser and the liquid line filter drier.

What are the different types of Receivers available in Dry All product range?

We have both Vertical and Horizontal type Receivers.

How do you select a Receiver Model?

First, one has to check the volume / holding capacity required. Receivers holding capacity is typically selected @110 % of total refrigerant charge. For example, if the refrigerant charge is 10 Kg, the receiver should have holding capacity of 11Kg. One has to also consider the Condensor size while calculating the receiver volume. Receiver inlet and outlet connection sizes should be in-line with the system liquid line tubing sizes.

In what capacity range are Dry All Accumulators available?

Dry All receivers’ off-the-shelf models are available from 1 Litre -25 Litre capacity. Customized models are available from 1 Litre – 50 Litre capacity.

What are the different types of INLET and OUTLET connections available in Dry All Receivers?

Solder & Roto-lock type connections from size 3/8” to 1-3/8” are available. Please refer Dry All catalog for more details.

What is the Maximum allowable pressure / Maximum Working Pressure of Dry All Receivers?

Yes, certain range of Dry All Accumulators are UL listed. The UL File number is SA45127-20181127

What are types of mounting / Fixing available in Dry All Vertical Type Receivers?

Two type of mountings are available:

  • a) Bolted & Nut (Stud type)
  • b) Mounting Flange

Does Dry All Receivers come with Sight Glass?

Models ranging from 15 Litre to 25 Litre come with sight glass.

Does Dry All Receivers come with provision for Fusible Plug / Pressure Relief Valve?

This provision is available on our LRRVD* Range of Receivers from 6 Litre – 12 Litre models only. *LRRVD-Deep Draw Type Receivers. This feature can be provided on all customized models. When system temperature or system pressure goes extremely high, a fusible plug / pressure relief valve respectively prevents the liquid receiver from bursting.

Do you make customized Receivers?

Yes, we make customized receivers as per customer design and specification. Please contact Dry All for more details on the process, models available, MOQ, Price, etc.